PROFIBUS
Protocol Information
Type of Network Device Bus, Process Control
Physical Media Twisted pair, fiber
Network Topology Bus
Device Addressing DIP Switch or hardware/software
Governing Body PROFIBUS&PROFINET International (PI)
Website www.profibus.com
Profibus electrical connector

PROFIBUS (Process Field Bus) is a standard for field bus communication in automation technology and was first promoted in 1989 by BMBF (German department of education and research) and then used by Siemens. It should not be confused with the PROFINET standard for Industrial Ethernet. PROFIBUS is not an openly published and royalty-free protocol as MODBUS.

Contents

Origin [edit]

The history of PROFIBUS goes back to a publicly promoted plan for an association started in Germany in 1987 and for which 21 companies and institutes devised a master project plan called "field bus". The goal was to implement and spread the use of a bit-serial field bus based on the basic requirements of the field device interfaces. For this purpose, member companies agreed to support a common technical concept for production (i.e. discrete or factory automation) and process automation. First, the complex communication protocol Profibus FMS (Field bus Message Specification), which was tailored for demanding communication tasks, was specified. Subsequently in 1993, the specification for the simpler and thus considerably faster protocol PROFIBUS DP (Decentralized Peripherals) was completed. Profibus FMS is used for (non deterministic) communication of data between Profibus Masters. Profibus DP is a protocol made for (deterministic) communication between Profibus masters and their remote I/O slaves.

There are two variations of PROFIBUS in use today; the most commonly used PROFIBUS DP, and the lesser used, application specific, PROFIBUS PA:

  • PROFIBUS DP (Decentralized Peripherals) is used to operate sensors and actuators via a centralized controller in production (factory) automation applications. The many standard diagnostic options, in particular, are focused on here.
  • PROFIBUS PA (Process Automation) is used to monitor measuring equipment via a process control system in process automation applications. This variant is designed for use in explosion/hazardous areas (Ex-zone 0 and 1). The Physical Layer (i.e. the cable) conforms to IEC 61158-2, which allows power to be delivered over the bus to field instruments, while limiting current flows so that explosive conditions are not created, even if a malfunction occurs. The number of devices attached to a PA segment is limited by this feature. PA has a data transmission rate of 31.25 kbit/s. However, PA uses the same protocol as DP, and can be linked to a DP network using a coupler device. The much faster DP acts as a backbone network for transmitting process signals to the controller. This means that DP and PA can work tightly together, especially in hybrid applications where process and factory automation networks operate side by side.

In excess of 30 million PROFIBUS nodes were installed by the end of 2009. 5 million of these are in the process industries.

Technology [edit]

PROFIBUS Protocol (OSI reference model)

OSI-Layer PROFIBUS
7 Application DPV0 DPV1 DPV2 Management
6 Presentation --
5 Session
4 Transport
3 Network
2 Data Link FDL
1 Physical EIA-485 Optical MBP


Application layer [edit]

To utilize these functions, various service levels of the DP protocol were defined:

  • DP-V0 for cyclic exchange of data and diagnosis
  • DP-V1 for acyclic and cyclic data exchange and alarm handling
  • DP-V2 for isochronous mode and data exchange broadcast (slave-to-slave communication)

Security layer [edit]

The security layer FDL (Field bus Data Link) works with a hybrid access method that combines token passing with a master-slave method. In a PROFIBUS DP network, the controllers or process control systems are the masters and the sensors and actuators are the slaves.

Various telegram types are used. They can be differentiated by their start delimiter (SD):

No data: SD1 = 0x10

SD1 DA SA FC FCS ED

Variable length data:

SD2 = 0x68

SD2 LE LEr SD2 DA SA FC DSAP SSAP PDU FCS ED

Fixed length data:

SD3 = 0xA2

SD3 DA SA FC PDU FCS ED

Token:

SD4 = 0xDC

SD4 DA SA ED

Brief acknowledgement:

SC = 0xE5

SC

SD: Start Delimiter

LE: Length of protocol data unit, (incl. DA,SA,FC,DSAP,SSAP)

LEr: Repetition of protocol data unit, (Hamming distance = 4)

FC: Function Code

DA: Destination Address

SA: Source Address

DSAP: Destination Service Access Point

SSAP: Source Service Access Point

SAP (Decimal) SERVICE
Default 0 Cyclical Data Exchange (Write_Read_Data)
54 Master-to-Master SAP (M-M Communication)
55 Change Station Address (Set_Slave_Add)
56 Read Inputs (Rd_Inp)
57 Read Outputs (Rd_Outp)
58 Control Commands to a DP Slave (Global_Control)
59 Read Configuration Data (Get_Cfg)
60 Read Diagnostic Data (Slave_Diagnosis)
61 Send Parameterization Data (Set_Prm)
62 Check Configuration Data (Chk_Cfg)

Note: SAP55 is optional and may be disabled if the slave doesn't provide non-volatile storage memory for the station address.

PDU: Protocol Data Unit (protocol data)

FCS: Frame Checking Sequence

ED: End Delimiter (= 0x16 !)

The FCS is calculated by simply adding up the bytes within the specified length. An overflow is ignored here. Each byte is saved with an even parity and transferred asynchronously with a start and stop bit. There may not be a pause between a stop bit and the following start bit when the bytes of a telegram are transmitted. The master signals the start of a new telegram with a SYN pause of at least 33 bits (logical "1" = bus idle).

Bit-transmission layer [edit]

Three different methods are specified for the bit-transmission layer:

  • With electrical transmission pursuant to EIA-485, twisted pair cables with impedances of 150 ohms are used in a bus topology. Bit rates from 9.6 kbit/s to 12 Mbit/s can be used. The cable length between two repeaters is limited from 100 to 1200 m, depending on the bit rate used. This transmission method is primarily used with PROFIBUS DP.
  • With optical transmission via fiber optics, star-, bus- and ring-topologies are used. The distance between the repeaters can be up to 15 km. The ring topology can also be executed redundantly.
  • With MBP (Manchester Bus Powered) transmission technology, data and field bus power are fed through the same cable. The power can be reduced in such a way that use in explosion-hazardous environments is possible. The bus topology can be up to 1900 m long and permits branching to field devices (max. 60 m branches). The bit rate here is a fixed 31.25 kbit/s. This technology was specially established for use in process automation for PROFIBUS PA.

For data transfer via sliding contacts for mobile devices or optical or radio data transmission in open spaces, products from various manufacturers can be obtained, however they do not conform to any standard.

PROFIBUS DP It runs over two core screened cable that is violet sheathed and its speed varies from 9.6Kbps to 12Mbps. A particular speed can be chosen for a network to give enough time for communication with all the devices present in the network. If systems change slowly then lower communication speed is suitable and if the systems change quickly then effective communication will happen through faster speed. The RS485 balanced transmission that is used in PROFIBUS DP only allows 32 devices to be connected at once but more devices can be connected and network can be expanded with the use of hubs or repeaters.

PROFIBUS PA It is slower than PROFIBUS DP and runs at fixed speed of 31.2Kbps via blue sheathed two core screened cable. The communication may be initiated to minimise the risk of explosion or for the systems that intrinsically need safe equipment. The message formats in PROFIBUS PA are identical to PROFIBUS DP.

Note: PROFIBUS DP and PROFIBUS PA should not be confused with ProfiNet. ProfiNet is an Ethernet communication standard and it is used for process control and process measurement. It is basically used to link computer systems in an office or a network.

Profiles [edit]

Profiles are pre-defined configurations of the functions and features available from PROFIBUS for use in specific devices or applications. They are specified by PI working groups and published by PI. Profiles are important for openness, interoperability and interchangeability, so that the end user can be sure that similar equipments from different vendors perform in a standardised way. User choice also encourages competition that drives vendors towards enhanced performance and lower costs.

There are PROFIBUS profiles for Encoders, Laboratory instruments, Intelligent pumps, Robots and Numerically Controlled machines, for example. Profiles also exist for applications such as using HART and wireless with PROFIBUS, and process automation devices via PROFIBUS PA. Other profiles have been specified for Motion Control (PROFIdrive) and Functional Safety (PROFIsafe).

Standardization [edit]

PROFIBUS was defined in 1991/1993 in DIN 19245, was then included in EN 50170 in 1996 and, since 1999, established in IEC 61158/IEC 61784.

Organization [edit]

The PROFIBUS Nutzerorganisation e.V. (PROFIBUS User Organization, or PNO) was created in 1989. This group was composed mainly of manufacturers and users from Europe. In 1992, the first regional PROFIBUS organization was founded (PROFIBUS Schweiz in Switzerland). In the following years, additional Regional PROFIBUS & PROFINET Associations (RPAs) were added.

In 1995, all the RPAs joined together under the international umbrella association PROFIBUS & PROFINET International (PI). Today, PROFIBUS is represented by 25 RPAs around the world (including PNO) with over 1400 members, including most if not all major automation vendors and service suppliers, along with many end users.

See also [edit]


References [edit]

  • [1] PROFIBUS system description
  • J. Weigmann, G. Kilian: Decentralization with PROFIBUS DP/DPV1, ISBN 978-3-89578-218-3
  • M. Felser: PROFIBUS Manual, A collection of information explaining PROFIBUS networks assembled by Prof. Max Felser, ISBN 978-3-8442-1435-2

External links [edit]


Original courtesy of Wikipedia: http://en.wikipedia.org/wiki/Profibus — Please support Wikipedia.
A portion of the proceeds from advertising on Digplanet goes to supporting Wikipedia.
4554 videos foundNext > 

Profibus DP

DeltaV Profibus DP demonstration.

Siemens S7 Profibus Tutorial Pt 24.avi

Expalnation of setting up a Profibus Network using DP DP Couplers.

One Minute RS-485: PROFIBUS

A brief overview of the transceiver characteristics for RS-485 based PROFIBUS applications.

Signal integrity verification on Profibus system

Bus systems are widely used for factory automation purposes. Downtime of the bus system may have a large negative impact on your production flow and producti...

Rosemount 3051 Profibus Pressure Transmitter: Making Configuration Easy - Technology Demo

Jesse Dodge explains how configuration of the Rosemount 3051 Profibus Pressure Transmitter using the easy-to-use Local Operator Interface (LOI). See how the ...

Profibus reduces your total cost of ownership

James Powell explains how process instruments with Profibus can reduce your total cost of ownership. www.siemens.com/profibus.

Comunicacion Profibus con Step 7 y el Software S7-PLCSIM Parte1.wmv

A contnuación, Voy a anexar links de los diferentes equipos que manejan en siemens para comunicación Profibus: http://www.automation.siemens.com/mcms/automat...

Vernetzung über Profinet / Profibus

Seit vielen Jahren gewinnt weltweit die Dezentralisierung bei Automatisierungsaufgaben immer mehr an Bedeutung. Der dezentrale Anlagenaufbau verringert den A...

RED PROFIBUS jos

video de la red profibus.

configuracion red profibus a variador de fecuencia MM440 siemens

se explica como configurar una red profibus dp ,para comunicar y manipular un variador de frecuencia micromaster 440 de siemens.

4554 videos foundNext > 

331 news items

Automation World

Automation World
Thu, 16 May 2013 08:11:20 -0700

Following the transition of the “Profibus Network Diagnostic, Maintenance and Troubleshooting” LinkedIn group to an Italian language only format, Ron Mitchell has launched “Profibusters”. This new group will “target topics that include commissioning, ...
 
Control Engineering Website
Tue, 14 May 2013 02:46:46 -0700

The Fisher FIELDVUE DVC6200p digital valve controller is built on Fisher's highly successful and innovative linkage-less, non-contact sensor technology. PROFIBUS users can now experience the performance and reliability demanded in today's process ...
 
Electropages (press release)
Thu, 16 May 2013 10:00:22 -0700

Innovasic has announced a new version of its RapID Platform Network Interface for PROFIBUS connectivity. The RapID Platform – PROFIBUS Network Interface supports all data rates up to 12Mbits/sec and is DP-V1 certified by PROFIBUS & PROFINET ...
 
Ferret
Wed, 15 May 2013 11:51:35 -0700

Hosted by Profibus Association of Australia and the PICC, the Profibus EXPO will include a round table discussion featuring technical experts representing the world's most popular communication protocols in process and factory automation. To be held in ...
 
Ferret
Wed, 24 Apr 2013 20:47:48 -0700

Profibus International Chairman Karsten Schneider has been confirmed as the inaugural keynote speaker at a series of business luncheons to be organised by Profibus Association of Australia and PACE magazine. Profibus and Profinet International (PI) is ...
 
Automation World
Tue, 21 May 2013 14:25:20 -0700

and compatibility with a variety of wired communication standards such as Foundation fieldbus, Hart, and Profibus. “ISA100.11a full functional field wireless network systems and devices make use of state-of-the-art dual redundant technologies that ...
 
Control Engineering Asia
Tue, 21 May 2013 09:02:03 -0700

There are more than 80 different module types to choose from for discrete, process, motion and specialty applications. In addition to CANopen and CC-Link, GE offers Profinet, Profibus DP, DeviceNET, Modbus/TCP, and Modbus serial. Share this article ...
 
Green Options (blog)
Mon, 20 May 2013 05:10:30 -0700

An external 24V supply ensures that if the 400V mains fail, control circuits will remain powered-up and Profibus communication is selected to allow the SCADA system to monitor all data within the system. Decentralised control. The choice of a ...