Modbus is a serial communications protocol originally published by Modicon (now Schneider Electric) in 1979 for use with its programmable logic controllers (PLCs). Simple and robust, it has since become a de facto standard communication protocol, and it is now a commonly available means of connecting industrial electronic devices.[1] The main reasons for the use of Modbus in the industrial environment are:

  • It has been developed with industrial applications in mind
  • It is openly published and royalty-free
  • It is easy to deploy and maintain
  • It moves raw bits or words without placing many restrictions on vendors

Modbus allows for communication between many (approximately 240) devices connected to the same network, for example a system that measures temperature and humidity and communicates the results to a computer. Modbus is often used to connect a supervisory computer with a remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems. Many of the data types are named from its use in driving relays: a single-bit physical output is called a coil, and a single-bit physical input is called a discrete input or a contact.

The development and update of Modbus protocols has been managed by the Modbus Organization since April 2004, when Schneider Electric transferred rights to that organization, signaling a clear commitment to openness.[2] The Modbus Organization is an association formed of independent users and suppliers of Modbus compliant devices that seeks to drive the adoption of the Modbus communication protocol suite, and its evolution to address architectures for distributed automation systems across multiple market segments.[3]

Contents

Communication and devices [edit]

Each device intended to communicate using Modbus is given a unique address. In serial and MB+ networks only the node assigned as the Master may initiate a command, but on Ethernet, any device can send out a Modbus command, although usually only one master device does so. A Modbus command contains the Modbus address of the device it is intended for. Only the intended device will act on the command, even though other devices might receive it (an exception is specific broadcastable commands sent to node 0 which are acted on but not acknowledged). All Modbus commands contain checking information, ensuring that a command arrives undamaged. The basic Modbus commands can instruct an RTU to change a value in one of its registers, control or read an I/O port, as well as commanding the device to send back one or more values contained in its registers.

There are many modems and gateways that support Modbus, as it is a very simple protocol and often copied. Some of them were specifically designed for this protocol. Different implementations use wireline, wireless communication, such as in the ISM band, and even SMS or GPRS. One of the more common designs of wireless networks makes use of the mesh topology. Typical problems the designers have to overcome include high latency and timing problems.

Frame format [edit]

All Modbus variants choose different frame formats.[1]

Modbus RTU Frame Format
Name Length Function
Start 3.5c idle at least 3-1/2 character times of silence (MARK condition)
Address 8 bits Station Address
Function 8 bits Indicates the function codes like read coils / inputs
Data n * 8 bits Data + length will be filled depending on the message type
CRC 16 bits Error checks
End 3.5c idle at least 3-1/2 character times of silence between frames
Modbus ASCII Frame Format
Name Length Function
Start 1 char starts with colon ( : ) (ASCII value is 0x3A)
Address 2 chars Station Address
Function 2 chars Indicates the function codes like read coils / inputs
Data n chars Data +length will be filled depending on the message type
LRC 2 chars Error checks
End 2 chars carriage return – line feed(CR/LF) pair (ASCII values of 0x0D & 0x0A)
Modbus TCP Frame Format
Name Length Function
Transaction Identifier 2 bytes For synchronization between messages of server

& client

Protocol Identifier 2 bytes Zero for Modbus/TCP
Length Field 2 bytes Number of remaining bytes in this frame
Unit Identifier 1 byte Slave Address (255 if not used)
Function code 1 byte Function codes as in other variants
Data bytes n bytes Data as response or commands

Unit identifier is used with Modbus/TCP devices that are composites of several Modbus devices, e.g. on Modbus/TCP to Modbus RTU gateways. In such case, the unit identifier tells the Slave Address of the device behind the gateway. Natively Modbus/TCP-capable devices usually ignore the Unit Identifier.

The byte order is Big-Endian (first byte contains MSB).

Note: The "Function code" field is part of the PDU and not part of the transport (TCP) header.

Supported function codes [edit]

The various reading, writing and other operations are categorised as follows.[4] The most primitive reads and writes are shown in bold. A number of sources [5] use alternative terminology, for example Force Single Coil where the standard uses Write Single Coil.

Function Name Function Code
Data Access Bit access Physical Discrete Inputs Read Discrete Inputs 2
Internal Bits or Physical Coils Read Coils 1
Write Single Coil 5
Write Multiple Coils 15
16-bit access Physical Input Registers Read Input Register 4
Internal Registers or Physical Output Registers Read Holding Registers 3
Write Single Register 6
Write Multiple Registers 16
Read/Write Multiple Registers 23
Mask Write Register 22
Read FIFO Queue 24
File Record Access Read File Record 20
Write File Record 21
Diagnostics Read Exception Status 7
Diagnostic 8
Get Com Event Counter 11
Get Com Event Log 12
Report Slave ID 17
Read Device Identification 43
Other Encapsulated Interface Transport 43

Implementations [edit]

Almost all implementations have variations from the official standard. Different varieties might not communicate correctly between equipment of different suppliers. Some of the most common variations are:

  • Data types
    • Floating point IEEE
    • 32-bit integer
    • 8-bit data
    • Mixed data types
    • Bit fields in integers
    • Multipliers to change data to/from integer. 10, 100, 1000, 256 ...
  • Protocol extensions
    • 16-bit slave addresses
    • 32-bit data size (1 address = 32 bits of data returned.)
    • Word swapped data

Limitations [edit]

  • Since Modbus was designed in the late 1970s to communicate to programmable logic controllers, the number of data types is limited to those understood by PLCs at the time. Large binary objects are not supported.
  • No standard way exists for a node to find the description of a data object, for example, to determine if a register value represents a temperature between 30 and 175 degrees.
  • Since Modbus is a master/slave protocol, there is no way for a field device to "report by exception" (except over Ethernet TCP/IP, called open-mbus)- the master node must routinely poll each field device, and look for changes in the data. This consumes bandwidth and network time in applications where bandwidth may be expensive, such as over a low-bit-rate radio link.
  • Modbus is restricted to addressing 247 devices on one data link, which limits the number of field devices that may be connected to a master station (once again Ethernet TCP/IP proving the exception).
  • Modbus transmissions must be contiguous which limits the types of remote communications devices to those that can buffer data to avoid gaps in the transmission.
  • Modbus protocol provides no security against unauthorized commands or interception of data.[6]

Trade group [edit]

The Modbus organization is a trade association for the promotion and development of Modbus protocol.

References [edit]

  1. ^ a b Bill Drury, Control Techniques Drives and Controls Handbook (2nd Edition) . 2009, Institution of Engineering and Technology, Online version available at: http://knovel.com/web/portal/browse/display?_EXT_KNOVEL_DISPLAY_bookid=2995&VerticalID=0, page 508 and following
  2. ^ Modbus Organization, Inc. "Modbus FAQ". Modbus FAQ. Modbus Organization, Inc. Retrieved 1 November 2012. 
  3. ^ Modbus Organization, Inc. "About Modbus Organization". About Modbus Organization. Modbus Organization, Inc. Retrieved 8 November 2012. 
  4. ^ Modbus Application Protocol V1.1b
  5. ^ Gordon Clarke, Deon Reynders Practical Modern Scada Protocols: Dnp3, 60870.5 and Related Systems ,Newnes, 2004 ISBN 0-7506-5799-5 pages 47-51
  6. ^ Charles Palmer, Sujeet Shenoi (ed) Critical Infrastructure Protection III: Third IFIP WG 11. 10 International Conference, Hanover, New Hampshire, USA, March 23–25, 2009, Revised Selected Papers Springer, 2009 ISBN 3-642-04797-1, page 87

External links [edit]


Original courtesy of Wikipedia: http://en.wikipedia.org/wiki/Modbus — Please support Wikipedia.
A portion of the proceeds from advertising on Digplanet goes to supporting Wikipedia.
11994 videos foundNext > 

All Need to Know About Modbus RTU

A Quick overview of Modbus RTU by John Rinaldi of Real Time Automation. www.rtaautomation.com.

Modbus Data structure

John Rinaldi of Real Time Automation describes Modbus data structures.

DEFCON 16: ModScan: A SCADA MODBUS Network Scanner

Speaker: Mark Bristow, Security Researcher ModScan is a new tool designed to map a SCADA MODBUS TCP based network. The tool is written in python for portabil...

All You need to know about Modbus TCP

A quick overview of Modbus TCP from John Rinaldi at rtaautomation.com.

Modbus communication between PLCs -- writing a bit

PLC control of a VFD via Modbus

Here, we are using an AutomationDirect ("CLICK") PLC to control the starting, stopping, and speed command of an AutomationDirect variable-frequency motor dri...

Modbus pulses on oscilloscope part1

How to connect an oscilloscope to display Modbus data signals (RS-485 pulses) using two channels -- differential signal measurement, not ground-referenced.

Rede de automação RS485/MODBUS com Arduino

Uma rede RS485 com um sistema supervisório (mestre) e um arduino (escravo). No escravo há um fan ("cooler") e um sensor de temperatura. O arduino foi program...

Modbus RTU: подключение контроллеров к SCADA TRACE MODE 6

Учебный фильм, обучающий подключению контроллеров к SCADA TRACE MODE 6 по протоколу Modbus RTU. Рекомендуется повторить действия в бесплатной инструментально...

Arduino ModBus Control

Arduino using ModBus protocol to control motor and servo. This system will be installed in an RC car with high hopes of SkyNET integration.

11994 videos foundNext > 

530 news items

MarketWatch (press release)

MarketWatch (press release)
Wed, 15 May 2013 08:21:41 -0700

The new converters expand SenGenuity's line of VisConnect(R) Converters to include the VC-2010 CANopen Converter, VC-2020 ASCII over RS-485 Converter, and VC-2030 MODBUS RTU over RS-485 Converter. Both the VC-2010 CANopen and VC-2030 ...

Automation World

Automation World
Mon, 22 Apr 2013 12:12:57 -0700

Get seamless integration by using our new MESR424 series Modbus Gateways to bridge RS-232, RS-422 or RS-485 devices on Modbus serial networks with those on Modbus TCP networks. The serial ports can be accessed over a LAN or WAN using Direct ...
 
Lainformacion.com
Thu, 16 May 2013 05:31:22 -0700

Vectron International presenta los conversores VisConnect® que utilizan ASCII y MODBUS RTU sobre RS-485. lainformacion.com. jueves, 16/05/13 - 14:30. [ ]. Vectron International, líder en el diseño, fabricación y comercialización de productos basados en ...
 
BFMTV.COM
Wed, 15 May 2013 20:15:37 -0700

Les nouveaux convertisseurs étendent la gamme SenGenuity des convertisseurs VisConnect® pour inclure le convertisseur ouvert VC–2010 CAN, le convertisseur VC–2020 ASCII via RS–485 et le convertisseur VC–2030 MODBUS RTU via RS–485.
 
ANSA.it
Wed, 15 May 2013 12:51:22 -0700

Vectron International presenta i convertitori di VisConnect® che supportano ASCII e MODBUS RTU su RS-485. Convertitori di nuovo protocollo interfacciano direttamente con i sensori di viscosità ViSmart® per il rilevamento e il controllo della viscosità ...
 
Automation World
Thu, 16 May 2013 22:14:33 -0700

All ViewMarq message displays are fitted with (1) RS-232, (1) RS-485, and (1) Ethernet port, and can be connected to a PLC, PC, or any device capable of serial ASCII master, Modbus RTU, or Modbus TCP communications. Programming the ViewMarq ...
 
Control Engineering Website
Fri, 17 May 2013 06:58:12 -0700

In addition to Profibus and Modbus units and a version with four galvanically isolated analog outputs, there are new models for Ethernet and Profinet IO, optionally with a robust die-cast zinc housing or 6TE DIN rail housing. The new Profinet boxes are ...
 
PACE Today
Fri, 17 May 2013 00:18:18 -0700

The simplicity of the system is derived from the interface between the control system and the gateway, for instance, Modbus or Profibus. The HART commands are mapped to the I/O register format of the interface protocol. The control system can then use ...